Skip to Content

KNX guides

KNX actuator types: switching, dimming, blinds and HVAC

Actuators are the KNX devices that do the work: they switch circuits, dim lights, move blinds and open heating valves. This guide explains the main actuator types, what to check for each load, and how to choose the right number of channels for a project.

1. What a KNX actuator does

Sensors such as push buttons, presence detectors and thermostats send telegrams to group addresses. Actuators listen to those group addresses and switch or control the connected load. Most actuators are DIN rail devices in the distribution board; flush-mounted actuators are used where a single load sits far from the panel.

2. Switch actuators

Switch actuators have relay outputs that switch loads on and off: lighting circuits, sockets, pumps or fans. They are sold with different numbers of channels and different rated currents per channel.

  • Check the rated current of each channel against the load, and the inrush current of LED drivers and electronic transformers. Many manufacturers state a capacitive load (C-load) rating for this.
  • Typical functions in the application program: on/off, time delay, staircase timer, logic, scenes, status feedback and, on some models, current detection.
  • Manual operation on the device helps during commissioning and when the bus is not yet programmed.

3. Dimming actuators

The right dimmer depends on the light source and how it is driven:

  • Universal (phase) dimmers for mains loads, with leading edge or trailing edge, for resistive, inductive or capacitive loads. Check the minimum and maximum load per channel and whether the LED lamps are dimmable.
  • LED dimmers with PWM outputs for constant-voltage LED strips (for example 12 V or 24 V), in single colour, tunable white or RGB(W) versions.
  • 0-10 V or 1-10 V control units that send an analogue control signal to compatible drivers.
  • DALI gateways that connect a KNX system to DALI drivers, so each luminaire or group can be dimmed and monitored over DALI.

4. Blind and shutter actuators

Blind actuators drive roller shutters, venetian blinds, awnings and curtains. Each channel controls one motor with separate up and down outputs.

  • Use the travel times set in the application program to move to a position in percent and, for venetian blinds, to set the slat angle.
  • Choose the actuator for the motor type: mains motors are the most common, and some actuators are made for low-voltage DC motors.
  • Only connect several motors to one channel when the motor manufacturer allows it.
  • Wind, rain and frost alarms from a weather station can move blinds to a safe position automatically.

5. Heating and HVAC actuators

  • Heating actuators drive electrothermal valve actuators on radiators or underfloor heating manifolds, usually with PWM or on/off control. Check whether the valves are 24 V or 230 V.
  • Fan coil actuators switch the fan speed stages and drive the heating and cooling valves of a fan coil unit.
  • Analogue output actuators provide 0-10 V signals for valves, dampers and other HVAC equipment.
  • Room temperature control comes from thermostats or push buttons with built-in controllers; split and VRF air conditioning is usually connected through a KNX gateway.

6. How to choose actuators for a project

  • List every load with its type (mains lighting, LED driver, motor, valve) and its current.
  • Group the loads by actuator type and count the channels, then add a reserve for later changes.
  • Check the space in the distribution board: DIN rail devices are sized in module widths.
  • Add the bus current of every actuator when you size the KNX power supply of each line.
  • Plan command and status group addresses for every channel before commissioning.