KNX universal actuator 12-way, 12 binary inputs, SD card – Eelectron IO12F01KNX-SD. Power supply: Via KNX bus, 21–32 V DC (SELV); Current consumption: ≤ 10 mA from bus; 10–30 mA for 50 ms during switching (ETS parameter); Outputs: 12 relays, 16 A cos φ 1 / 8 A cos φ 0.6 at 230 V AC; Inputs (digital mode): 12 dry-contact inputs (SELV circuits), scanning voltage 3.3 V DC, max cable length 30 m (98 ft) twisted.
| Power supply | Via KNX bus, 21–32 V DC (SELV) |
|---|---|
| Current consumption | ≤ 10 mA from bus; 10–30 mA for 50 ms during switching (ETS parameter) |
| Outputs | 12 relays, 16 A cos φ 1 / 8 A cos φ 0.6 at 230 V AC |
| Max relay current | 16 A / 16 AX (140 µF); minimum switching current 10 mA |
| Max peak current | 165 A / 20 ms |
| Max total current for the device | 180 A |
| Terminals | Max 2.5 mm² (approx. 14 AWG) solid or stranded |
| Inputs (digital mode) | 12 dry-contact inputs (SELV circuits), scanning voltage 3.3 V DC, max cable length 30 m (98 ft) twisted |
| Inputs (analog mode) | NTC probes TS01A01ACC (-20 to +100 °C), TS01B01ACC (-50 to +60 °C); max cable length 30 m (98 ft) twisted |
| SELV outputs | Outputs may be connected to SELV circuits only if all outputs on the same level (1–6 or 7–12) are SELV |
| Group addresses / associations | 250 / 250 |
| Mounting | DIN rail, 6 modules; LV distribution switchboard |
| Enclosure | PC-ABS, IP20 (EN 60529) |
| Operating temperature | -5 °C to +45 °C (23 °F to 113 °F) |
| Storage temperature | -20 °C to +55 °C (-4 °F to 131 °F) |
| Relative humidity | max 90 % non-condensing, indoor use |
| Standards | EN 63044-3; EN 63044-5-1 / EN 63044-5-2; EN 50491-2; LVD 2014/35/EU; EMC 2014/30/EU |
| Certifications | KNX certified; CE |
| ETS application | F-series universal actuator application (ETS 5 or later) |
| Weight (net) | 0.5 kg (1.10 lb) |
Specifications
| Channels | 12 relays, 16 A cos φ 1 / 8 A cos φ 0.6 at 230 V AC |
| Mounting | DIN rail, 6 modules; LV distribution switchboard |